MNS Low Voltage Draw out Switchgear 3.0

Share
Rated voltage

Rated insulation voltage

100OV AC,3P,150OV DC*
Rated operating voltage690V AC,3P,750V DC*
Rated impact withstand voltage6/8/12 kv*
overvoltage level Ⅱ/Ⅲ/Ⅳ*
Pollotion level3
Rated frequency60HZ
Rated currentMain busbar
rated current
7300A

rated peak withstand current
264KA

rated short-time withstand current

12OKA.1S
100KA,3S


Distribution busbar
rated current
2000A


rated peak withstand current
220KA


rated short-time withstand current
10OKA,1S

Anti-fault arc
rated woring voltage
690V


Expected short circuit current100KA


Duration300ms


Judgment criteria
Arc class c


  • Product Description
  • Main Features

MNS Low-voltage extraction switchgear is mainly composed of some combined motor control units and other functional units. These units are mounted in a closed metal cabinet by overlapping the upper and lower parts. Each cabinet body is connected with a horizontal bus set above the cabinet body, and the functional units of the same cabinet body are connected with a vertical bus in parallel. The cabinet body is divided into four isolation zones: horizontal bus zone, vertical bus zone, cable zone and equipment installation zone. Functional units are installed in their respective small rooms. When any functional unit has an accident, it will not affect other units and prevent the accident from expanding

1.Anti arc design and complete type testing to ensure the safety of operators

2.2. Effectively prevent temperature rise, overvoltage, and seismic resistance, ensuring the continuous operation of equipment 

3.Multiple flexible combinations of side outlet, rear outlet, back-to-back, and other O以ions to adapt to various spaces

4.Modular design has a compact structure, saves space, is easy to upgrade and transform.and reduces design time 

5. Extractable design with better availability and interchangeability, reducing losses caused by downtime maintenance

6. Plug一 in and fixed design can provide customers with more choices, taking intc account system reliability, availability, and flexibility, to meet various working conditions and userneeds 

7. Intelligent temperature measurement technology, real-time monitoring of key component temperatures, reducing the risk of power failure